Cable voltage drop calculator (DC, single-phase and three-phase)

Estimate voltage drop in copper or aluminium cable for DC, single-phase and three-phase circuits, with resistivity corrected for conductor temperature and optional reactance.

Runs in your browser. What you enter stays on this page and is not uploaded.

Estimate only. This calculates the voltage drop from the formula and stated resistivity; it is not a cable-sizing or code-compliance tool.
Distance from supply to load, not the loop length.
Line-to-line for three-phase.
20 °C for a cold cable; 70 °C (PVC) or 90 °C (XLPE) at full load; NEC tables use 75 °C.
About 0.08 mΩ/m for multicore cables; 0 ignores it.

Showing the worked example. Results update as you type.

Result

A 6.44% drop exceeds the 5% commonly recommended for a whole installation (3% for lighting circuits in IEC 60364-5-52 Annex G for a public supply; the US NEC informational notes suggest 3% per branch and 5% overall).

Voltage drop7.726 V6.44% of 120 V
Voltage at the load112.27 V
Conductor resistance6.337 Ω/km1.932 Ω/1000 ft at 75 °C, 3.309 mm²
Power lost in the cable154.5 W2 conductors × I² R L
  • Copper (annealed, 100% IACS): ρ₂₀ = 0.017241 Ω·mm²/m, α₂₀ = 0.00393 /K, R(T) = ρ₂₀ (1 + α₂₀ (T − 20 °C)) / A.
  • ΔV = 2 × I × L × (R cos φ + X sin φ) with L the one-way length.
  • This estimates the drop only. It does not check ampacity, installation method, grouping, short-circuit or protective-device rules; size cables with your local wiring code and the cable maker’s data.

Method and limits

The drop along a run of one-way length L carrying current I is

ΔV = k × I × L × (R cos φ + X sin φ)

with k = 2 for DC and single-phase circuits (current flows out and back) and k = √3 for a balanced three-phase circuit (giving the line-to-line drop). For DC, cos φ = 1 and X = 0. R is the resistance of one conductor per metre at its operating temperature:

R(T) = ρ20 (1 + α20 (T − 20 °C)) / A

using ρ20 = 0.017241 Ω·mm²/m and α20 = 0.00393 /K for annealed copper (IEC 60028) and ρ20 = 0.028264 Ω·mm²/m and α20 = 0.00403 /K for aluminium (IEC 60889).

Worked example: a 120 V single-phase circuit, 20 A, 100 ft one-way of 12 AWG copper at 75 °C. R = 1.93 Ω per 1000 ft (the NEC Chapter 9 Table 8 value), so ΔV = 2 × 20 A × 100 ft × 1.93 Ω/1000 ft = 7.73 V, 6.4% of 120 V: too much for the 3% branch-circuit guidance.

The power lost in the cable is the number of current-carrying conductors × I² R L.

Limits

Steady current, a balanced three-phase load and uniform conductor temperature are assumed; skin and proximity effects (significant above about 150 mm² at 50/60 Hz) and harmonic currents are ignored. Typical limits are 3% for a branch circuit and 5% overall (NEC informational notes), or 3% for lighting and 5% for other uses from a public supply (IEC 60364-5-52 Annex G). This tool does not check current-carrying capacity, installation method, grouping, fault loop impedance or protective devices.