Cable voltage drop calculator (DC, single-phase and three-phase)
Estimate voltage drop in copper or aluminium cable for DC, single-phase and three-phase circuits, with resistivity corrected for conductor temperature and optional reactance.
Runs in your browser. What you enter stays on this page and is not uploaded.
Showing the worked example. Results update as you type.
Result
A 6.44% drop exceeds the 5% commonly recommended for a whole installation (3% for lighting circuits in IEC 60364-5-52 Annex G for a public supply; the US NEC informational notes suggest 3% per branch and 5% overall).
- Copper (annealed, 100% IACS): ρ₂₀ = 0.017241 Ω·mm²/m, α₂₀ = 0.00393 /K, R(T) = ρ₂₀ (1 + α₂₀ (T − 20 °C)) / A.
- ΔV = 2 × I × L × (R cos φ + X sin φ) with L the one-way length.
- This estimates the drop only. It does not check ampacity, installation method, grouping, short-circuit or protective-device rules; size cables with your local wiring code and the cable maker’s data.
Method and limits
The drop along a run of one-way length L carrying current I is
ΔV = k × I × L × (R cos φ + X sin φ)
with k = 2 for DC and single-phase circuits (current flows out and back) and k = √3 for a balanced three-phase circuit (giving the line-to-line drop). For DC, cos φ = 1 and X = 0. R is the resistance of one conductor per metre at its operating temperature:
R(T) = ρ20 (1 + α20 (T − 20 °C)) / A
using ρ20 = 0.017241 Ω·mm²/m and α20 = 0.00393 /K for annealed copper (IEC 60028) and ρ20 = 0.028264 Ω·mm²/m and α20 = 0.00403 /K for aluminium (IEC 60889).
Worked example: a 120 V single-phase circuit, 20 A, 100 ft one-way of 12 AWG copper at 75 °C. R = 1.93 Ω per 1000 ft (the NEC Chapter 9 Table 8 value), so ΔV = 2 × 20 A × 100 ft × 1.93 Ω/1000 ft = 7.73 V, 6.4% of 120 V: too much for the 3% branch-circuit guidance.
The power lost in the cable is the number of current-carrying conductors × I² R L.
Limits
Steady current, a balanced three-phase load and uniform conductor temperature are assumed; skin and proximity effects (significant above about 150 mm² at 50/60 Hz) and harmonic currents are ignored. Typical limits are 3% for a branch circuit and 5% overall (NEC informational notes), or 3% for lighting and 5% for other uses from a public supply (IEC 60364-5-52 Annex G). This tool does not check current-carrying capacity, installation method, grouping, fault loop impedance or protective devices.
References
- NFPA 70 (National Electrical Code): Chapter 9 Table 8 conductor properties and the voltage-drop informational notes
- Schneider Electric Electrical Installation Guide (IEC 60364 practice, voltage-drop limits and formula)
- Voltage drop: DC and AC formulas
- Electrical resistivity and its temperature coefficient (copper 1.724 × 10⁻⁸ Ω·m, α = 0.00393 /K)
Related tools
- Ohm’s law and power calculatorEnter any two of voltage, current, resistance and power to get the other two, with SI prefixes such as mA, kΩ and µW.
- Resistor colour code calculator (4, 5 and 6 band)Read a 4-, 5- or 6-band resistor colour code, or find the bands for a value, with tolerance, temperature coefficient and the nearest E-series value.
- Voltage divider calculatorCalculate the output of a two-resistor voltage divider with or without a load, or find the bottom resistor for a target voltage with the nearest E24 and E96 values.
- LED series resistor calculatorFind the series resistor for one LED or a string of LEDs from the supply voltage, forward voltage and current, with the next standard value and its power rating.
- RC and RL time constant calculatorTime constant τ = RC or L/R with the charge and discharge percentages at 1τ to 5τ, the value at any time and the −3 dB cut-off frequency.
- Capacitive and inductive reactance and resonant frequency calculatorCapacitive reactance 1/(2πfC), inductive reactance 2πfL, LC resonant frequency, characteristic impedance and series Q.